Oil-Immersed transformer
Conservator-Type Oil-Immersed Transformer
Oil preservation with room to breathe.
Three-phase oil-immersed transformers with an external conservator tank, copper windings and a Buchholz relay for reliable protection against internal faults.
- Rated power
- 25 – 2,500 kVA
- Voltage class
- up to 36 kV
- Cooling
- ONAN
- Standard
- IEC 60076 · EN 50464-1
Supplied with routine test records, GA drawing and O&M documentation. Special tests available on request.
Overview
Engineering detail, without the guesswork.
The conservator arrangement allows the oil volume to expand and contract while keeping the main tank fully filled. This makes the platform well suited to larger ratings, higher ambient temperatures and installations where oil condition and gas monitoring are part of the maintenance regime.
Available from 25 kVA to 2,500 kVA in standard loss series, or configured to project-specific losses and dimensions.
Standard features
- HV bushings according to DIN 42531 or EN 50180
- LV bushings according to DIN 42530 or EN 50386
- Off-circuit tap changer in 5 positions
- Corrugated-wall steel tank
- Thermometer pocket (contact thermometer from 630 kVA)
- Lifting lugs and earthing terminals
- Filling plug and drain cock
- Bi-directional rollers, 90°
- Conservator tank with oil level indicator
- Buchholz relay (standard from 1,000 kVA)
- Copper windings
Model range
Standard configurations
Indicative values for standard designs. Final dimensions, losses and weights are confirmed at design review.
| Model | Rated power | HV | LV | Impedance | Total weight |
|---|---|---|---|---|---|
| PS-OC-100 | 100 kVA | 11 kV | 0.4 kV | 4% | 680 kg |
| PS-OC-250 | 250 kVA | 11 kV | 0.4 kV | 4% | 1,220 kg |
| PS-OC-400 | 400 kVA | 11 kV | 0.4 kV | 4% | 1,350 kg |
| PS-OC-630 | 630 kVA | 11 kV | 0.4 kV | 4% | 1,800 kg |
| PS-OC-1000 | 1,000 kVA | 11 kV | 0.4 kV | 6% | 2,450 kg |
| PS-OC-1600 | 1,600 kVA | 11 kV | 0.4 kV | 6% | 3,850 kg |
| PS-OC-2500 | 2,500 kVA | 11 kV | 0.4 kV | 6% | 5,670 kg |
Need a rating outside this table? Every product is available as an engineered variant.
Ask about custom ratingsExplore further
Related equipment
Next step
Need this unit configured for your site?
Send the rating, voltage ratio and site constraints. We will check the design against your duty and come back with a firm proposal.