Oil-Immersed transformer
Hermetically Sealed Oil-Immersed Transformer
Sealed for life. Built for demanding industrial duty.
Three-phase distribution transformers with copper windings, sealed and oil-filled under vacuum for maintenance-free operation in demanding environments.
- Rated power
- 25 – 2,500 kVA
- Voltage class
- up to 36 kV
- Cooling
- ONAN
- Standard
- IEC 60076 · EN 50464-1
Supplied with routine test records, GA drawing and O&M documentation. Special tests available on request.
Overview
Engineering detail, without the guesswork.
Designed for mounting in complete transformer substations and on steel-lattice poles, the range is manufactured to EN 50464-1 with losses configured to suit your duty cycle. The corrugated-wall tank provides the cooling surface without external radiators, keeping the footprint compact and the unit robust in transit.
Every unit is routine tested before dispatch, with optional heat-run, impulse and noise measurements available on request.
Standard features
- HV bushings according to DIN 42531 or EN 50180
- LV bushings according to DIN 42530 or EN 50386
- Off-circuit tap changer in 5 positions
- Corrugated-wall steel tank
- Thermometer pocket (contact thermometer from 630 kVA)
- Lifting lugs and earthing terminals
- Filling plug and drain cock
- Bi-directional rollers, 90°
- Safety valve
- Copper windings
Model range
Standard configurations
Indicative values for standard designs. Final dimensions, losses and weights are confirmed at design review.
| Model | Rated power | HV | LV | Impedance | Total weight |
|---|---|---|---|---|---|
| PS-OH-100 | 100 kVA | 11 kV | 0.4 kV | 4% | 620 kg |
| PS-OH-250 | 250 kVA | 11 kV | 0.4 kV | 4% | 1,110 kg |
| PS-OH-400 | 400 kVA | 11 kV | 0.4 kV | 4% | 1,420 kg |
| PS-OH-630 | 630 kVA | 11 kV | 0.4 kV | 4% | 1,800 kg |
| PS-OH-1000 | 1,000 kVA | 11 kV | 0.4 kV | 6% | 2,810 kg |
| PS-OH-1600 | 1,600 kVA | 11 kV | 0.4 kV | 6% | 3,700 kg |
| PS-OH-2500 | 2,500 kVA | 11 kV | 0.4 kV | 6% | 5,600 kg |
Need a rating outside this table? Every product is available as an engineered variant.
Ask about custom ratingsExplore further
Related equipment
Next step
Need this unit configured for your site?
Send the rating, voltage ratio and site constraints. We will check the design against your duty and come back with a firm proposal.